SE400 (400W)
SE400 Features
Pure sine wave output (THD < 5% @ , linear load @ 12.5V / 25V / 50V).
Power ON / OFF remote control (Green Terminal).
Input & output fully isolation.
Output frequency 50/60Hz selectable by DIP switch.
Output voltage / power saving mode selectable.
Input protection: Reverse Polarity (Fuse) / Under Voltage / Over Voltage.
Output protection: Short Circuit / Overload / Over Temperature.
Power saving mode < 2W.
FCC / CE approved.
MODEL | SE400-112, SE400-124, SE400-148, SE400-212, SE400-224, SE400-248 |
---|---|
Main Features | ◎ Output frequency and output voltage selectable |
AC Output Voltage | 100/110/115/120 VAC; 200/220/230/240 VAC |
Rated Power | 400VA |
Surge Power | <800VA |
Output Waveform | Pure Sine Wave (THD < 5%@ Normal Load) |
Frequency | 50/60 Hz ± 0.5% |
DC Output Voltage | ─ |
DC Output Voltage Range | ─ |
DC Input Voltage | 12V; 24V; 48V |
DC Input Voltage Range | 10.5~16VDC; 21~32VDC; 42~64VDC |
Efficiency | 88%; 89%; 90%; 88%; 89%; 90% |
Operating Temperature | -20~40℃, Power De-rating from 40°C~60°C |
Storage Temperature | -30~70℃ |
Safety | CE / FCC |
Dimension (WxHxD) | 150x68x187 mm |
Weight (Net) | 1.3 kg |
Socket Type | GFCI / NEMA 5-15R / GE / AU / UK / France Connector / Universal |